English edition · cyberattaques.org in FrenchFrançais
Vulnerability

Danfoss AK-SM 8xxA controllers up to 5.4.0 hit by unauthenticated stack buffer overflow

CISA has flagged a stack-based buffer overflow in an unauthenticated CGI handler of Danfoss AK-SM 8xxA controllers that could allow code execution with webserver privileges. Versions up to 5.4.0 are affected, and Danfoss says a fix will ship in an upcoming 5.5.x release.

What to do now Illustration photo (industrial refrigeration control panel)
CVSS severity9.3Critical
EPSS probability1 %
ExploitationNot observed
PatchNone
Product
Danfoss AK-SM 8xxA Series
Affected versions
AK-SM8xxA versions 5.4.0 and earlier
Fixed in
Fix announced for an upcoming 5.5.x release (not yet published)
CVE
CVE-2026-129713

On 24 November 2026 CISA released an advisory covering Danfoss AK-SM 8xxA Series controllers, which are used in commercial facilities and deployed worldwide. The issue, tracked as CVE-2026-129713, is a stack-based buffer overflow (CWE-121).

The bug sits in a CGI handler that does not require authentication. A remote attacker can send it specially crafted HTTP or HTTPS POST requests. According to the advisory, this corrupts memory and forces the webserver to restart, and could hypothetically lead to arbitrary code execution with the webserver's privileges. No credentials are needed.

All AK-SM8xxA releases up to and including 5.4.0 are listed as affected. No fixed build was available when the advisory was published: Danfoss says the flaw will be addressed in an upcoming 5.5.x software release for the AK-SM 800A Series, without giving a release date.

Danfoss also plans to remove the option for users to disable Strict Mode in future releases. The advisory does not explain how that mode relates to this specific flaw. Carlo Meijer of Midnight Blue reported the vulnerability.

Until the update ships, CISA points to its standard guidance for control systems: keep these devices off the internet, put them behind firewalls isolated from business networks, and use more secure remote access methods where remote access cannot be avoided.

Action plan

What to do now

  1. Inventory Danfoss AK-SM 8xxA controllers and identify any running version 5.4.0 or earlier.
  2. Confirm that none of these controllers' web interfaces are reachable from the internet and block any direct exposure.
  3. Place the devices behind a firewall, separated from the business network, and restrict HTTP/HTTPS access to administration hosts only.
  4. Watch for unexpected webserver restarts on the controllers, which may indicate exploitation attempts.
  5. Track Danfoss announcements and install version 5.5.x as soon as it is released.